It is assumed that your Com’X 210/510 Gateway already collects data from your meter(s). If not, read and understand Schneider manuals for installing, operating, or maintaining your Com’X 210/510 Gateway. Installation and program procedures must be carried out and inspected by qualified personnel. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with this product.

Step 1: Configure your Com’X 510 Gateway

The Com’X allows you to export device logs via HTTP. To do so, please follow the instructions you can find below. 

Connect your Com'X gateway to Wattics energy analytics software
Connect to your Com’X webpage by entering the device’s IP address into a browser address bar. The default login credentials are:

  • Username: admin
  • Password: admin

(See corresponding numbered steps in screenshot above for guidance)

1. Go to Settings> General Settings > Publication

2. Select CSV export as the Destination platform in the drop-down list

3. Select how often you want the data logs to be exported to Wattics: Hourly, Daily, Weekly, Monthly, or Logging interval. Wattics supports all time intervals so you can select based on your requirements.

4. Select HTTPS as the Protocol.

5. In the Server field, enter web-collector.wattics.com

6. In the Port field, enter 443

7. Click Yes for Authentication Required

8. For User login and User password, enter the username and password provided by Wattics

9. For the Path field, enter: /measurements/v2/comx

10. Set the Field name to file.

11. Set Compression activated to No.

12. Set Field separator to Comma.

13. Set Decimal separator to Dot.

14. Set Date Format to DD-MM-YYYY.

15. Click Save changes to save the HTTPS Export configuration.

Your data logs will now be sent to Wattics, to check that all went okay, you’ll need to log into your Wattics dashboard and check the data monitor for incoming readings. 

Please note:

  • Before checking that your data is streaming correctly, you need to have at least one or more data points created in your dashboard.
  • The first readings to come in could take as long as the logging interval you selected for data exports.

If you would like further information about connecting your Schneider Com’X device to Wattics, please leave us a request, using the form below:

     

    Schneider Integrations

    Schneider TAC Xenta 411 via Octopus Gateway

    Schneider PowerLogic EGX300 Gateway via FTP

    Schneider PowerLogic PM8000 meter via Obvius AcquiSuite EMB A8810 Gateway

    Schneider Com’X 510 via FTP

    Contact us to get a quote or a custom-tailored demonstration with one of our business advisors.

    +353 1415 1242
    info@wattics.com
    Contact us

    Create your own integration

    Not supported yet? Don’t be left behind and integrate now

    Go to the page

    Energy Learning community online

    Be part of the big picture, share your knowledge and get access to experience and expertise from others

    Visit our forum

    Subscribe to our blog

    Sign up to keep up-to-date with what’s happening within the industry

    Subscribe